ESP Fireline 2 Zone Fire Alarm Optical Kit 2
Contents Of ESP Fireline 2 Zone Fire Kit 2:
Panel Features:
- 2 programmable zones
- Activate end of line monitoring
- 30 fire detectors per zone
- Unlimited number of call points per zone
- Integral manual alarm button
- 'Class change' facility
- Enable/disable security key
- One man walk test facility
- Fire volt free change over relay
- Fault volt free change over relay
- Individual sounder circuit fault ID
- Individual zone/sounder isolate
- BS5839 and EN54 compliant
- CE certified
- Requires only 1x12v battery
- ABS casing
| INPUTS |
Max detectors per zone |
30 |
|
Thresholds for zone conditions |
0-2 mA (Fault condition) 2-6 mA (Normal condition) 6-110 mA (Fire condition) 110 mA Short (Short condition) |
| POWER |
Mains fail consumption |
50mA |
|
Mains Supply |
230 VAC ± 10% |
|
Standby supply |
1 x 7ah 12V S.L.A. Battery |
|
Power availability |
0.7 amps |
| OUTPUTS |
Sounder 1 |
24V (max 300mA fused) |
|
Sounder 2 |
24V (max 300mA fused) |
|
Fault Relay |
Volt free 500mA (maximum load) |
|
Auxiliary output |
24VDC (300mA fused) |
| ENVIRONMENT |
Working Temperature |
0 to 40°C |
|
Storage Temperature |
-20 to 60°C |
|
Humidity |
0-95% |
|
Dimensions (mm) |
340W 290H 100D |
|
Weight |
2.1 KG |
-
0 stars
No reviews have been written yet
-
-